BA series - rated breaking capacity - alarm auxiliary switch

Main technical parameters:Rated working voltage: DC80V AC1 20/240V、AC240/415V、AC250V、AC277/480YVMechanical/electrical lifespan: 10000/6000 cycles, (electrical lifespan of UL489A products: 1000 cycles)


Main technical parameters:

  • Rated working voltage: DC80V AC1 20/240V、AC240/415V、AC250V、AC277/480YV

  • Mechanical/electrical lifespan: 10000/6000 cycles, (electrical lifespan of UL489A products: 1000 cycles)

  • Rated insulation voltage: AC415V; Rated impulse withstand voltage: 2500V

  • Rated breaking capacity


Rated voltage

(V)

Rated current

(A)

Extreme numbers

Breaking ability (A)

TUV,CE,CCC

UL1077

UL489A

UL489

Icn

Inc

DC80

0.5-50

1,2,3

4000

5000

5000 U1

5000

/

AC250

0.5-50

1

4000

5000

/

/

/

AC415

0.5-50

2,3

4000

5000

/

/

/

AC120/240

0.5-50

1,2,3

/

/

5000 U1

/

5000